Our first member has completed his initial evaluation of the Stargate SG3000. An excerpt from that evaluation:
I worked with the Star Gate 3000 today. I decided to check the system at my own house. Many a Testo and Digi-Cool have been tested there, so I am very familiar with the system.
First things first, I have tested Digi-cool, Testo, Refco, Field Piece, and JB. If there is any common theme I have seen with digital gauges, is the fact that the pressures are almost always identical, something will not find with bourdon tube gauges.
When I started this post, I was going to focus on the mechanical aspect of the product. The construction of the instrument is solid. I do not like the fact that it comes without a manifold and the fact that the temperature sensors have a very large mass and takes a considerable amount of time to change, but it is what it is, and I decided to look at it from a technical standpoint. At the end of the day, if the instrument reduces callbacks, and makes the techs more confident in their work, I figured I could live with the design.
The primary purpose of the SG 3000 seems to be to make the refrigerant charging process easier, faster correct and in real-time. As the load changes, the target SH is recalculated and the technician simply watches the display to determine if the system charge is high, low or OK.
If you have ever used the Carrier or Trane charging calculators, and WB and DB thermometer, you will understand the concept easily. The problem with any of these charts is the load is a dynamic thing. As the load in the house changes, so does the target SH, so the SG3000 by design would seem to minimize footsteps through the house to measure WB, and also eliminate the technician having to calculate required SH and any errors that might result. Additionally measuring WB in the R/A duct where it should be measured provides a much more representative picture of the load the system is seeing if the airflow is correct.
I got a chuckle when reading the instructions as they say “Prior to using the SG3000 make sure that:
• The air conditioning system is operating in accordance with manufacturers specifications.
• All coils are clean and free flowing
• Outside temperature is above 55 degrees F
• ect
I am thinking “I’m hooking it up to make it operate in accordance with the manufacturers specifications”
You still need a very competent technician at the helm. The SG3000 will do what it is designed to do, and do it flawlessly. It is not an intuitive instrument, but does come with good instructions both written and illustrated. The keypad and probe designation are a little quirky, but after a few times it is easy to use. The SG 30000 calculates a target superheat for the indoor WB conditions and outdoor air temperature. It does not consider however the operating load, (More on this to follow.). So if the system requires 8 degrees of superheat, when the SG3000 measures that SH, as you correct the refrigerant level, the charge will go from high or low to OK.
Before I go into the design flaw I see with this product, I feel everyone needs to be on the same page with my thinking. so, back to the basics.
Read more of our Exclusive Instrument Evaluations and the full Evaluation of the Stargate® SG3000™ only athttp://www.hvacprotech.comThe Source.
We get alot of emails from tech’s asking the differences in the Testo First and Second Generation 523’s, the 556 and the 560’s. This article will be a very basic summary of those differences. Keep in mind the Testo 500 Series RSA’s are complex, advanced refrigeration system diagnostic instruments - in particular the 556 and the 560. Each can be fully customized and configured to suit literally every field application. We strongly recommend that prior to making an investment in any of these three instruments that you contact TRUTech Tools athttp://www.trutechtools.comThey will discuss with you in detail the capabilities, available configurations and make a customized package recommendation designed for each technician’s specific requirements. We also, obviously recommend registering at HVACPROTech.com and accessing the most complete, unbiased data based on FieldTests and member evaluations of these instruments available anywhere on the internet.
Testo 523: Generation 1
The First Generation 523 is no longer in production and is not available directly from Testo. It is still available, in limited quantities from TRUTech. If you are considering the transition from analog to digital manifold gauge technology this is definitely an option that merits consideration. The First Generation 523 was originally marketed under the trade name Testo Kool and depending upon where and when you purchased it listed for anywhere from $700.00 up to $1050.00. This version was an exceptionally advanced instrument, particularly in consideration of it’s release date and in comparison to the alternative standard at the time, the analog manifold gauge. From a strictly physical appearance perspective, as you can see below - the First and Second Generations hold little resemblance to one another.
The Second Generation 523 display screen is significantly larger. The valve handles recess, the vertical structure of the case has been refined to include slightly concaved recesses on either side for easier handling. The Second Generation is a sleeker, refined, modern and by the description of some who have evaluated it a ”sexier” looking design
When you look past the appearances there are differences in the 1rst and 2nd Generations that merit mentioning. The 1rst Gen. 523 was equipped with the capability to data log - a capability and a function that has widely beed used as a diagnostics tool in commercial applications for many, many years, and one whose effectiveness and versatility is very quickly being discovered by the technician community. This capability was ”designed out” of the 2nd Gen. 523 - it it’s place the option of communicating the systems operational parameters via infrared signaling to a thermal printer was designed in. The 2nd Generation 523 can be purchased with the infrared printer included with the instrument or without it. A sidenote that I find an admirable quality in Testo is the fact that their IR platform accomodates all IR compatible instruments in their line, so in this case one size really does fit all. Additional less than obvious differences are the change in sensors. The 1rst Gen utilized an absolute pressure [http://en.wikipedia.org/wiki/Absolute_pressure]sensor, whereas the 2nd Gen utilizes a relative pressure [http://en.wikipedia.org/wiki/Relative_pressure] sensor. A “nulling” [ refer to this article: http://digitalzeus.wordpress.com/2008/01/09/digital-gauge-dictionary-zeroed-or-nulled/to learn more about the relevance of nulling ], value was also designed in to the instrument. The final note relevant to the 1rst Gen 523 is applicable to all digital manifold gauges, but specifically those that are housed or left seated in a poly case, such as those the 500 Series RSA line is packaged in. When charging liquid into a system, with the manifold gauge seated in it’s case an inherent risk of damage as a result of static discharge [see the demonstration below] is present.
The entire Second Generation 500 Series RSA’s have enhanced protection in comparison to their First Generation counterparts against static discharge damage. [It is still our recommendation, even given the enhanced protection that the RSA be removed from it's case and hung from the equipment to establish a ground path when charging liquid into the equipment]. The last remaining available original, in the box ”Testo Kool” 523’s that I am personally aware of are available from TRUTech. TRUTech offers the option of either purchasing the base 523 [without data logging support peripherals ie., software and cable] for approximately $350.00 - it is also available with data logging support peripherals for approximately $425.00. A PROTech highly recommended value.
Testo 523: Generation 2
If you’ve spent 10 minutes around computers, then you’ll know when you see the familiar little v. that it is representative of a version change - that can be interpreted in one of two ways, depending I suppose on whether you are an optimist or a pessimist. It can mean either new and improved or broken and fixed. Both of those analogies can be applied to the Second Generation 523. Originally introduced as the RSA 523 v. 2.00 - the instrument was recalled due to a potential issue relevant to manifold integrity and the concern that refrigerant loss was a possibility, the resulting correction was the addition of a hose port protective skirt, [see the side by side illustration below]:
Aside from the above noted revision there are no physically distinguishable differences in v. 2.00 and v. 2.01of the 2nd Gen 523. [This revision was actually academic, and was obviously made at no cost to the technician - the only reason it merits mentioning is to caution the technician that may consider purchasing this instrument from a source that is not recognized as an authorized source, as an example, from a private seller on EBay. If you see this instrument without it's protective skirting, there is the possibility of known refrigerant loss at the manifold ports]. The second and as of the date of publish of this article, the final revision made to the 2nd Gen. 523 was a firmware flash. This revision also requires the instrument be returned to Testo New Jersey for implementation. Even though the 523 is primarily marketed as a residential applications instrument [an inaccurate characterization, in my experience], FieldTesting of the 523 revealed that it’s refresh or update rate was not adequate in setting or varifying intricate pressure controls like those typically found in commercial and transport refrigeration equipment, [a side by side illustration of the refresh rate prior to flashing and following flashing is below]:
This revision, by means of a firmware flash resulted in the designation of the RSA 523 v. 2.02. The following data relevant to the features and capabilities of the 2nd Generation 523 v. 2.02, in the quoted areas are extracted from the TRUTech Tools website, remember TRUTech builds and esigns custom RSA packages. Specific accessories included with TRUTech custom packages are not reflective of all autorized distributors of these instruments. TRUTech typically excels in both value and support and service, if you do not intend to purchase this instrument from them consult the vendor of your selection.
Unparalled Features:
1.Ability to print the measurement results on site via wireless printer
3.Large backlit display, and intuitive user operation
4.Three and four valve designs are available with a 3/8-evacuation port on four valve manifolds
5.High durability valve handles with Teflon seats
6.Backlit sight glass and display
7.Hose holder with integrated LCD protection
8.Pre loaded refrigerants: 30
No other product made can compete at any level. Testo has taken a quantum leap forward in AC/R measurements allowing the lab technician or service technician to deliver consistently accurate results to owners, manufacturers and end users of air conditioning and refrigeration equipment
Superheat and Subcooling Measurement: Thirty on board temperature pressure charts provide unparalleled detail and accuracy of refrigerant saturation temperatures, superheat and subcooling. Unlike traditional paper charts no interpolation of the temperature-pressure relationship is required. It is now possible to measure and set superheat and subcooling with laboratory accuracy in the field as the Testo 523 reads pressures and temperatures to the tenth of a psi and tenth of a degree and automatically calculates real-time superheat and subcooling values. Temperature measurement is just as critical as pressure when commissioning and servicing equipment.
Temperature: The platinum based (platinum film on a ceramic substrate) 4-wire construction, of the spring loaded temperature sensor (Pt-100) has a very low mass (yielding a fast response) and is not affected by stray voltages that may be present on the refrigeration equipment. Unlike traditional K-type thermocouples, the sensor is electrically isolated from the RSA. Isolating the temperature sensor electrically form the system eliminates the possibility of incorrect temperature measurement resulting from stray electrical currents or ghost voltages often present on improperly grounded refrigeration and air conditioning systems. Because the resistance of a Pt100 sensor bears an absolute relationship to temperature (unlike a thermocouple whose output depends on the difference between the hot junction and cold junction) no special compensating circuit needs to be provided in the electronics. In short, the Pt100 has a wide operating range, excellent accuracy, good linearity, excellent physical strength, long-term stability, and is the preferred sensor for all industrial processes where accuracy and repeatability are required. Additionally, Pt100 probes may be replaced without recalibration of the RSA instruments. Sensors are available in lengths up to 40 feet. The Velcro-elastic strap provides insulation from ambient air along with positive contact to the refrigeration line from ¼” to 3” in diameter. Air and immersion probes are available to further enhance your testing applications.
Time: Incorporated into the system analyzer is a new dimension; time. The entire new generation of RSA products incorporates a real time clock that permits accurate documentation of the time and date readings were recorded via the wireless printer or data logging. Testo was first-to-market with a complete line of refrigeration system analyzers that incorporate data logging, and now the first to bring wireless printing to the complete line. Owners of Testo combustion or other test equipment that already use a wireless printer will benefit from cost savings, as the printer is universal to all Testo products. A printout of the final operating parameters on all RSA products allows for field documentation of operating at system startup or pre and post operation.
The Testo 523digital refrigeration/air conditioning system analyzers are a multipurpose tool designed for every day use replacing a gauge manifold, superheat or subcooling thermometers, pressure-temperature charts, etc.. with a rugged hand held versatile tool.
Included in the kit:
523 RSA & Pipe Clamp Probe
Hose Keeper/ Screen Protector Accessory
Note that while the package above is infrared ready, it is not equipped with the infrared thermal printer. This is an available option or the printer can be purchased ata later date.
Testo 556/560 : Generation 2
Seem like too much information yet? The 523 was the easy part. The instrument capabilities as well as complexities drastically increase with the 556/560 models. Selection of either of these two instruments is where the importance of configuration packages become critical, and as we have several times prior, strongly recommend you contact TRUTech Tools for guidance and recommendations relevant to your specific applications and the peripherals you will want to include with your individual configuration package.
The 556 and the 560 repectively, are referred to as a professional and planned service instrument and a professional, planned service and commissioning instrument. So what seperates the 556 from the 523 - the 556 incorporates a 4 valve manifold [below with a 3/8" service port], configuration (with illuminated sight glass), whereas the 523 manifold configuration is 2 valve.
The 556 also facilitates the potential to connect a total of 4 temperature probes. Wireless temperature measurements can be acquired from a distance of 65.616′ unobstructed.
When used in tandem with optional EasyKool software a total of 60,000 readings can be stored and referenced. An exceptionally wide variety of accessories are available to complement the 556 for virtually any known application. A list of these accessories is provided below. One of the reasons, assuming you’ve noticed, that the 556 and the 560 are often referenced in unison (556/560} is due to the fact that a single capability seperates the two. The 560 is available with a high quality pressure sensor to facilitate acquisition of absolute pressure and the display of corresponding evaporation temperature of water.
The 556/560 are each divided into two seperately designated appendices to their base model designations that should be noted. Base instrument model designations may be followed by either a 1 or a 2, (556-1 | 556-2), (560-1 | 560-2) - in both instances these appendices designate the refrigerant application suitability. [1] indicates a brass instrument that is suitable for at least the 30 refrigerant profiles [profiles listed below] included with the RSA Series, excluding NH3. The designation of numeral [2] indicates a stainless steel version designed for use in NH3 applications.
The data in the thumbnails below are specification sheets and available Accessory options. Click on the thumbnails for a full sized view of each document.
Testo RSA 523 | 556 | 560 Specification Sheet
Testo RSA 523 | 556 | 560 Accessory Profiles
Please remember this is a very limited, brief overview of the differences seperating Generational changes and model features and capabilities. This article should not be used to determine the configuration you will need for your individual applications. I very strongly recommend, if you are considering the purchase of either the 556/560, that you give TRUTech Tools a call and discuss your applications requirements and your own personal preferences relevant the what you want to be able to do with the instrument and what you may not want. Talk to Jim, tell him Zeus sent you. Contact information is available athttp://www.trutechtools.comand remember for real world field experiences and capabilities of these and other instruments -http://www.hvacprotech.com
I’m new to the boards here and I’m not sure if this is the section I should post this in, so if I’m mistaken, please correct me.
I received the 556-1 wireless kit the recently and today was the first chance that I got to use it. The first machine it saw was a 3 ton coolair split that is having occaisional low pressure lock out problems. I’m the third tech on this call and I have not seen the machine until today so I figure this will be a good opportunity to see what this DRSA is all about.
Right off the bat it’s plain to see that this instrument, yes instrument is not for every job. It is rather bulky ( when in case ) and I can’t see techs climbing up and down ladders and running around mechanical rooms with it on a daily basis. I don’t know about you but I like to travel light and usually only carry a small tool bag. I’ll go back to the truck if I think I need gauges. All of my work is commercial and more often then not the problem is electrical in nature. Besides I think that most of us here can tell if a unit is running okay just by feel alone.
With that in mind I have to say that this is the first set of digital gauges that I have ever used and you know what ? I like them. On the call I was on today first tech says TXV is bad, second tech says unit is under charged and has dirty condenser coil. I check and find 125 foot pipe run, 2 liquid line driers ( one at c/u and one inside a/h ), poor airflow evap and excessive pressure drop at a/h. what the 556 allowed me to do was measure pressures,superheat and sub cooling at both locations record them and download them to my laptop all on site. Gauging up was easy and most important of all, quick. The ability to record and transfer the data gathered is not to be underestimated.
The 556 seems rugged enough for its intended use and was relatively easy to set up initially. The display is clear and easy to read and the backlight worked very well. What a pleasure it was to actually see superheat and subcool values along with pressure without having to stop and consult pt chart and then do calculation. I can see that the accuracy of this instrument is a vast improvement over analog gauges. I can tell you that I checked system with my Y/J manifold and when I disconnected them the low side gauge needle was stuck at 15 psi. They were less then a month old and weren’t dropped that I know of. If I wasn’t convinced before I am now.
Read More of This Evaluation at HVACPROTech.com®
The Only Professional Technicians Boards with Comparative Instrument Analysis
Everyone - This is exactly what i’m trying to get at. It is s fact of life in most companys that you can’t always get the same tech back to the same call. The variability of readings across different gauges and techs is what I would like to see minimized. I Know that for a purely empirical test of analogs vs digital ( excuse me DRSA’s ) I would absolutely agree that duplicating sensor locations and hose connection locations is rule # 1.
The very reason that i even purchased the 556 was so that i could develop some level of confidence in the readings taken by multiple techs across all types of equipment in sometimes less than optimal conditions. Some techs have $400 multi sensor temp kits, some are using fieldpiece, one kid even showed me where he tucked the tip of his pocket digital thermometer under the suction piping insulation. Add to that the inaccuracy inherent in analogs and we can all see that is time for a change.
Field Applications
Hello everyone – today was the third time i have used the 556. today’s patient was a 80 ton Trane water cooled VAV unit with four compressors, each with single circuit. Age of unit is appx 20 years old. Several of these units have developed leaks and I havn’t found them all yet. I’ve used electronic leak detectors, Halide torches, bubbles and dye. As this is typical of the type of service work most of us encounter I thought it would be a good trial for the 556.
The 556 is rugged and appears well suited to field use. It is very easy and intuitive to use and dare I say fun. What a pleasure it is to watch s/h & s/c readings in real time. Here is a picture of the setup I used before the TESTO arrived.
I underestimated the time saved and ease of gauging up to equipment.. I attached wired probe to LL line and wireless probe to suction line. I left radio handle inside unit and it broadcasted temp signal to 556 flawlessly. Yesterday I could not get it to read s/h & s/c values. Then I realized that I forgot to enter refrigerant type. After that okay. Here is a picture of both the old way and the new way of checking charge. I like the new way better.
The only place to find hard field data on the diagnostics instruments you use. HVAC PROTech.com®http://www.hvacprotech.com
I find no particular enjoyment in closing an Evaluation thread in this manner. The motivating factor driving the concept of our FieldTest Boards was and is to inform, advise and illustrate the capabilities of any of the Tools and Instruments that we elect to evaluate in real world conditions, I mean what better testing grounds than the field - the sun, the rain, the snow and the mud that we as technicians are exposed to every single day. Ideally these fieldtests contribute valid data when the technician is determing the value that any given instrument may hold for his particular application(s) - and subsequent decisions to either purchase or not purchase the instrument is made as a result of being informed on those capabilities as they compare to instrument cost.
We don’t add every OEM that approaches us with an instrument or new tool that they want to include in this process. We have declined participation by more than one OEM as a result of preliminary research that we do prior to putting it into rotation for our members to evaluate. Poor product support, poor after sales service, sub-standard components, inadequate specifications, inadequate distribution lines are all among the reasons that we may elect to decline an OEM’s participation in the fieldtests. A subsequent result of that “screening” process has been the association of the HVACPROTech name with cutting edge, premium diagnostics instrument OEM’s. Our current rotation includes the Testo 330-1 LL and 327-1 Combustion Analyzers, the Testo 318-V Optics Inspection Scope, the Testo Second Generation RSA 523, the First Generation J/B DM-2 Intelligent Manifold, the Second Generation J/B DM-4 Intelligent Manifold, The Yellow Jacket 40802 DRSA, the StarGate SG 3000 and we are adding the Testo 556 and Testo 435 as well as the Digi-Cool 1250 DRSA.
One of the instruments that we elected to add to our rotation that did not meet all of our initial criteria for participation was the Refco Digimon - I will not henceforth refer to it as a digital manifold gauge nor an instrument, because unfortunately it does not fit the description of either. This is the first of all of the tools we have evaluated that we have stamped with our “Rejected” and “Failed” tags. The HVACPROTech Boards and her members are very proactive advocates of digital technology.
Digital instrumentation provides the technician with the resources to accurately apply the skills of his craft more reliably, every time he applies them in the diagnostics process. It’s good for business, it’s good for the trade, it’s good for the industry and most importantly it’s good for the tchnician. Digital instruments are also not inexpensive. The components that combine into a system that ultimately result in the instrument are often proprietary, high quailty sensors that have literally required years, and years and years of design and refinement and committment by the respective OEM to viably put reliable versions into our hands and subsequently into the field.
Not withstanding the reluctance of some of our members to include the Digimon in our evaluations - we elected to do so because they promised everything I listed in the above paragraph, with a 2 year warranty and at a reasonable - albeit unrealistic cost - we should have heeded our reluctance. Hindsight is 20/20. Refco specifications and in-house fieldtesting data for the Digimon was for all intents and purposes non existent. Promises were made relevant to the delivery of the Digimon that were not kept - not by vendors but by highly placed Refco employees. Those facts alone should have been red flags to begin with.
Typically this evaluation wuld have been confined to the HVACPROTech Boards - but the general consensus was to propogate it, so the information would be available to all of our trade brothers. It is our sincerest wishes that each of you will heed the information contained within this post in your decision to purchase this particular instrument.
In closing this preface to the closing of this thread. I would also remind each of you to note the vendor of this product and be mindful of the role they have elected to assume in the scenario below. A critical component in the equation of the transition from analog to digital instrumentation is the source you elect to purchase from. Without support and service from both the OEM and their selected representatives, this technology is as ineffective as the analogs they were meant to replace. The following is the final in a series of threads made by one of our members - leading to the termination of this FieldTest. Caveat Emptor brother.
Main Entry: 1fail
Pronunciation: \fāl\
Function: verb
transitive verb
1 a: to disappoint the expectations or trust of b: to miss performing an expected service or function for
2: to be deficient in : lack
3: to leave undone : neglect
4 a: to be unsuccessful in passing b: to grade as not passing
Main Entry: 1re·ject
Pronunciation: \ri-jekt\
Function: transitive verb
1:obsolete : to cast off
3: throw back, repulse
4: to spew out
The Review:
I called Refco today…they called back…yes we got your gauges in…
around noon get another call from Refco….their is a part broken off the bottom…and “something” rattling around inside the gauges…obviously they have been dropped….and there for the warranty is VOID!!!!
I explain to them that I did not drop the gauges…and THAT Johnston’s will VERIFY that their were NO parts broken off of the gauges when I gave them to them….maybe damaged in shipping?? Well part was inside the box….but gauges were bubble wrapped so could not have been damaged in shipping….so NO WARRANTY!…but were in 1 piece when Johnston’s shipped them…no got a broken piece inside the box….so how do you explain that? No telling…but flat out REFCO WILL NOT REPAIR OR REPLACE THE GAUGES!. OH If you want them back you pay shipping.
Ask for name of supervisor…ILL post that and e-mail address in a min.
So Call Local Johnston’s (Melbourne Florida 321-676-4177)..Talk To manager Mark.. we have a problem with vendors doing this Ill check into it and get back with you…but not much we can do…..he never called me back….so I take it as “sucks to be you” response…
So any way Get the name of Mr. in charge of REFCO for USA…but he’s traveling until Wednesday….
Steve Secord (1-800-848-4232)..secretary Cindy I believe…same one who passes me off to Keith the head tech who said no warranty.. said Steve Secord is traveling until Wednesday…”I can call him back then”…guess they cant take a message at refco
So got Steve’s e-mail address…if anyone cares…
f.secord@refcoswiss.com
I have not tried it yet…a little too pissed off to compose and e-mail that is more than POS and shove the things up your 1@#$$…..sooo Ill try the e-mail later….
Bottom line.
Johnston’s says yes gauges were in 1 piece when shipped. but can NOT do anything about refco refusing to honor warranty.
REFCO says…we don’t care what Johnston’s says..broke now warranty is VOID…if you want you are POS gauges back you pay shipping..
I’m out $226 bucks….that’s real money on [Edited] pay…so torqued off is an understatement….but only thing I can do is warn others NOT TO BUY REFCO Junk….Ill call Steve Wednesday…don’t see it doing any good…but something to do…
IF any of you know someone higher up in refco..or Johnston’s and need my real name…or address….the moderators know it and can release it to anyone they know….
The Refco Digimon® will be added to our line of FieldTest Instruments in approximately one month. I spoke with the Refco USA director this afternoon and he advised they will be mailed to my address to begin the FieldTest process.
The technical and specifications data I have available is probably no more inclusive than that already available to everyone here. I did want to kick the thread off though so we can have a list of testing members ready when the set arrives, so like all of the FieldTest threads, review our Protocol & Policies Statement [Note that I am revising frequency times relevant to posting your opinions and experiences with the FieldTest Instruments]. If you are able to agree to them and wish to participate, add your name to this thread.
A couple of caveats. (1). Refco readily admits that the Digimon® digitals are targeted at the typical residential technician. These sets were not intended for commercial applications.
(2). There is also a designed in update rate of 3 seconds - again this is acknowledged by Refco and was designed in to the set to provide a more fluid display of pressure.
If you are researching the Digimon® for possible purchase, they are not suitable to commercial environments.
The limited information I have available at the time this is published is the following:
The set is loaded with 50 refrigerant profiles, including R410A
SH/SC Measurable [Independently]
Vacuum Display
Protected LCD Screen
Illuminated [Backlit] Display
3 Second Update
Automatic Calibration
Auto-Off
Battery Level Indicator
Refrigerant Updates Available
Swiss Made
360° Swivel Hook
Clear Easy to Read Display Screen
Tried and Trusted Piston Valves
Ergonomic Hand Wheels
Accuracy +<>- 1%
Pressure Indication: bar/psi/kPa/MPa
Temperature Reading: °C/°F
Vacuum Measurement: mbar/Microns
Operating Temperatures: -20°C to +50°C/-4°F to +122°F
..If you look at a superheat charging chart for a fixed orifice system, you quickly see the required superheat varies with outdoor and indoor conditions. As the outdoor temperatures vary, so does the required superheat…pretty much the same relationship for indoor temperatures. Why? The net force pushing liquid through the metering device is the difference [...]
Unless you’ve been living under a rock for the past several years, you know R-22 is on the way out and R-410A appears to be the manufacturer’s weapon of choice for heat pump and comfort cooling equipment. If you’ve already encountered a 410A system and had a less than pleasant experience, possibly attempting to correct [...]
One of the more frustrating and difficult situations with heat pump diagnostics is open circuits in the control wiring. There is a logical process to follow when attempting to locate the failure…
No doubt, my most frustrating service issue has been locating refrigerant leaks. And I’ll be the first to admit it was due to my own ignorance, from simply not doing a little research. I started out with a cold sensor technology electronic detector, bought a second cold sensor electronic detector and eventually concluded electronic detectors [...]
A common failure with residential equipment condenser and blower motors is not actually the motor, but the run capacitor. Probably the majority of the time, the capacitors fail “open”…the motor can’t develop the necessary torque to actually begin rotation. So, it justs sits in a “stalled” condition, pulling above normal amps…the video gives some thoughts [...]
The Pt100 temperature probe on the Testo 500 series refrigeration instruments has been carefully designed to work under a wide range of applications while providing the fastest temperature response in the industry. The platinum based 4 wire construction of the sensor has exceptionally low mass and is shielded from electrical interference from ghost voltages or static electricity [...]
Some thought on combustion testing.
When performing a combustion test, one of the most important concepts to understand is stability of the combustion process. If the combustion process is not stable, it is not safe. Once a flame is established, the burner should quickly reach study state operation and not be affected by factors external to it.
While [...]
Why test?
Making and interpreting measurements is a crucial part of any job involving service, installation, design verification, engineering, or factory support of HVAC/R equipment. When it comes to verifying proper operation of the installed equipment it is critical that measurements made in the field are just as accurate as those made the laboratory. At Trutech we [...]
It has been four years since the US introduction of the first generation of Testo refrigeration products. Our new generation of the Testo line of refrigeration system analyzers (RSA’s) will continue to change the way the HVAC/R world troubleshoots, commissions and services AC & refrigeration systems. Although the first generation of refrigerant products was highly [...]